Test periods and currents for gG and gM fuse links
as per VDE 0636 Part 10 and VDE 0636 Part 201
Rated current In with gG test period test current
Characteristic current
Ich with gM 1) Inf If
A h
In ≤ 4 1 1.50 In 2.1 In
4 < In < 16 1 1.50 In 1.9 In
16 ≤ In ≤ 63 1 1.25 In 1.6 In
63 < In ≤160 2 1.25 In 1.6 In
160 < In ≤400 3 1.25 In 1.6 In
400 < In 4 1.25 In 1.6 In
1) Ich: with gM fuse links the time/current characteristic is specified through gates in Table 3 DIN VDE 0636 Part 10.
With short-circuit current, fuses limit the short-circuit current before the peak value is
reached, see current limitation diagram, Fig. 7-7.
Fuse links whose rated currents are in the ratio of 1:1.6 respond selectively up to
690 V rated voltage at rated currents ≥ 16 A.